-40%

ABB ACS800-U31-0030-5 AC ULH Drive, 3ph 30hp Industrial Machine Controller

$ 2904

Availability: 100 in stock
  • All returns accepted: Returns Accepted
  • Return shipping will be paid by: Buyer
  • Type: General Purpose AC Drive
  • Input Voltage: 208-690 VAC
  • Brand: ABB
  • Condition: New, in original box.box opened to verify and photograph contents
  • Item must be returned within: 30 Days
  • Refund will be given as: Money Back
  • MPN: ACS800-U31-0030-5
  • Restocking Fee: No
  • Model: ABB ACS800-U31-0030-5
  • Maximum Load: 30 HP

    Description

    ABB ACS800-U31-0030-5, Wall-Mounted Drive Ultra Low Harmonic , ACS800, 30 HP, Output Current: 45 A, 480 VAC , Voltage Range: 380-500V, NEMA 1 / UL Type 1 (IP21), Wall-mounted, Local or Remote Mounted LCD Display and Keypad, 0030 KVA, 3-Phase Input, 3-Phase Output, Frame: R5, Product HxWxD: 32.12 in x 10.43 in x 15.35 in, Product Weight: 144 lbs
    Brand: ABB
    Model Number: ACS800-U31-0030-5
    Item Category: Drives
    Subcategory: AC
    Series: ACS800 ULH
    Input Range VAC: 380 to 500 Volts AC
    Input Phase: 3
    HP (CT): 25 Horsepower
    Amps (CT): 37 Amps
    HP (VT): 30 Horsepower
    Amps (VT): 45 Amps
    Max. Frequency: 300 Hertz
    Braking Type: Flux Braking;Dynamic Braking Transistor Optional (External)
    AC Line Regenerative: No
    Closed Loop: Optional
    Motor Control-Max Level: Direct Torque Control
    Operator Controls: Keypad Included
    IP Rating: IP21
    NEMA Rating: NEMA 1
    Comments: Advanced Control Panel incl. graphic backlit display capable of displaying 3 values or bar graphs.
    Mounting: PANEL
    Frame Size: R5
    H x W x D: 32.1 in x 10.4 in x 15.4 in
    Net Weight: 144 lb
    ACS800-U31-0030-5 PC-Tool Software
    ACS800 has four different programs that allow the user to do a wide variety of things:
    DriveWindow
    Software designed for online ACS800 drive commissioning and maintenance purposes. Connection to the drive is through a USB card and high speed fiber optic cable. The drive requires an optional RDCO-0x adapter to support the fiber optic connection. Adjusting parameters, reading actual values, trending and graphing actual values is also possible.
    DriveWindow Light
    Software designed for ACS800 online drive commissioning and maintenance purposes. Connection to the drive is through an RS-232 connection to the panel port. Requires additional hardware for panel port connections. It is possible to adjust parameters, read the actual values, trend and graph actual values.
    DriveAP
    Software programming package for utilizing the 15 PLC-like programmable blocks included with ACS800 standard drive firmware. This is a graphical programming tool for the adaptive programming feature.
    DriveBrowser
    Software is designed for online drive commissioning and maintenance purposes. DriveBrowser uses a computer's standard Ethernet port to an EtherNet/IP or Modbus-TCP drive network. The drives require configuration and connection to an EtherNet/IP or Modbus-TCP network.
    Other ACS800-U31-0030-5 ACS800 Features
    1. Main Connection
    Voltage and Power Range
    3-phase 208 to 240 V ± 10%, except -U7/07, -07LC, -17, -37
    3-phase 380 to 415 V ± 10%
    3-phase 380 to 500 V ± 10%
    3-phase 525 to 690 V ± 10%
    Frequency
    48 - 63 Hz
    Power Factor
    cosϕ1 = 0.98 (fundamental)
    cosϕ = 0.93...0.95 (total)
    Power Factor ACS800-U11/ -U31/ -17/ -37
    cosϕ1 = 0.98 (fundamental)
    cosϕ= 0.93 to 0.95 (total)
    Efficiency (at nominal power)
    ACS800-Ux
    98%
    ACS800-1x/ -3x
    97%
    2. Motor Connection
    Frequency
    0...±300 Hz
    (0...±120 Hz with optional du/dt filters)
    Field Weakening Point
    8...300 Hz
    Motor Control
    ABB’s Direct Torque Control (DTC)
    3. Environmental Limits
    Temperature
    Transport
    -40 to +70°C
    Storage
    -40 to +70°C
    Operation
    -15 to +50°C no frost allowed
    +40 to +50°C at reduced output current (1% / 1°C)
    0 to +55°C no frost allowed
    ACS800-07LC
    +45 to +55°C at reduced output current (0.5% / 5°C)
    Cooling Method
    Dry clean air
    Direct liquid-cooling ((ACS800-07LC)
    +48°C max converter circuit, fresh water
    +42°C to +48°C at reduced output current
    4. Enclosure
    Ingress Protection
    IP21, IP22, IP42, IP54, IP54R, IP55
    5. Programming
    PC
    DriveWindow
    DriveWindow Light
    DriveAP
    DriveBrowser
    6. Fieldbus Connectivity
    Built-in
    None
    Optional
    CANopen
    ControlNet
    DeviceNet
    EtherCAT
    EtherNet/IP
    Modbus RTU
    Modbus TCP
    PROFIBUS DP
    ProfiNet I/O
    7. Application Features
    Compact Size, Everything Integrated
    Less space and installation work required. No need to install extra components such as input chokes or EMC filter.
    Built in Harmonic Filter in all ACS800 Drives
    Low harmonics, meaning less interference and less heating in cables and transformers. Filter also protects the drive from line side transients.
    Wide Range of Options Available
    Standard solutions available from ABB to met most customers application needs.
    Versatile Braking Options
    Optimal braking options are always available.
    No need for an external braking c hopper thus reducing size and installation cost.
    User Friendly Customer Interface
    Easy and fast commissioning and operation.
    Clear, alphanumeric display with start-up assistant that guides through the start-up procedures.
    Easy to use PC tools available for commissioning, maintenance, monitoring and programming.
    Versatile Connections and Communications
    Standard I/O covers most requirements. Connectable to commonly used fieldbuses.
    Extensive Programmability
    Flexibility. Possible to replace relays or even a PLC in some applications.
    Two levels of programmability
    Parameter programming (standard).
    Adaptive programming (free block programming): standard feature, more blocks available as options, all I/Os are programmable.
    Wide Power and Voltage Range
    One product series can be used to meet all application needs, meaning less training and spare parts and standardized interface to drives
    Wide Range of Robust Enclosures Available
    Industrial suitable solutions available for different environments including UL Type 1, UL Type 1 filtered, UL Type 12
    Robust Main Circuit Design
    Suitable for heavy industrial use. Reliable. Long motor cables can be used without extra output filters. Advanced thermal model allows high overloadability.
    Extensive Protection Features
    Enhanced reliability, fewer process interruptions. Possibility to also protect motors and process. Several adjustable limits to protect other equipment included.
    Galvanic Isolation of I/O
    Safe and reliable operation without separate isolators and relays.
    All Terminals Designed for Industrial Use
    Sufficient size even for large aluminum cables.
    No need for special tools in I/O cabling.
    8. Maintenance & Diagnostics
    Data Logging
    PC software for drives available for maintenance and monitoring.
    Built-in data and fault loggers are able to monitor signals and real-time status of a drive.
    9. Standards Compliance
    CE
    UL
    CSA
    C-Tick
    GOST R
    EMC according to EN 61800-3 (2004)
    1st environment, restricted distribution, category C2 as option up to 1000 A input current.
    2nd environment, unrestricted distribution, category C3 - standard in -07 (frame size nxR8i), -07LC, -17, and -37 (frame size R7i - nxR8i), option in the others